360kW / 450kVA Cummins Diesel Generator Set
With 50Hz operation, 1500 r/min rated speed and 380/400/415V voltage options, the SC500 generator set is suitable for factories, construction sites, mining projects, oilfield facilities, commercial buildings, data centers and emergency backup power systems.
- Prime power: 360kW / 450kVA; standby power: 400kW / 500kVA
- Powered by Cummins KTA19-G3 diesel engine
- 50Hz, 1500 r/min, 380/400/415V
- Turbocharged and aftercooled engine for reliable performance
- Open type, silent type and super silent configurations available
- Standard single-unit control system with LCD display and protection functions
- ATS, remote monitoring, trailer, soundproof enclosure and synchronizing system available as options
- Factory-tested at 0%, 25%, 50%, 75%, 100% and 110% load before delivery
Technical Specifications
| Item | Specification |
| Genset Model | SC500 |
| Prime Power | 360kW / 450kVA |
| Standby Power | 400kW / 500kVA |
| Frequency | 50Hz |
| Rated Speed | 1500 r/min |
| Rated Voltage | 380/400/415V |
| Power Factor | 0.8 |
| Operation Temperature | <= 40 deg C |
| Altitude | <= 1000 m |
| Relative Humidity | <= 60% |
Size and Weight
| Configuration | Dimensions L x W x H (mm) | Weight (kg) |
| Open Type | 3600 x 1355 x 1910 | 3970 |
| Silent Type | 5100 x 1385 x 2280 | 5200 |
| Super Silent Type | 5500 x 2040 x 2520 | 7492 |
Engine Specifications
| Item | Specification |
| Engine Brand | Cummins (CCEC) |
| Engine Model | KTA19-G3 |
| Aspiration | Turbocharged and aftercooled |
| Cooling Method | Water cooling |
| Cylinder Arrangement | 6 cylinders, in-line |
| Displacement | 19 L |
| Bore x Stroke | 159 mm x 159 mm |
| Compression Ratio | 13.9:1 |
| Rated Speed | 1500 r/min |
| Engine Prime / Standby Power | 403kW / 448kW |
| Dry Weight | 2676 kg |
| Fuel Consumption at Standby Power | 91 kg/h |
| Fuel Consumption at 100% Prime Power | 82 kg/h |
| Fuel Consumption at 75% Prime Power | 62 kg/h |
| Max Allowable Exhaust Back Pressure | 10 kPa |
| Maximum Intake Air Restriction – Dirty Filter | 6.23 kPa |
| Maximum Intake Air Restriction – Clean Filter | 3.73 kPa |
| Coolant Capacity – Engine Only | 30.3 L |
| Thermostat Range | 82-93 deg C |
| Minimum Pressure Cap | 48 kPa |
| Maximum Allowable Temperature – Standby / Prime | 104 / 100 deg C |
| Lubrication Oil Capacity | 38.6 L, subject to final technical confirmation |
| Battery Recharge | 24V / 35A |
| Minimum Battery Capacity (CCA) | 900 CCA, subject to final technical confirmation |
Alternator Specifications
| Item | Specification |
| Rated Voltage | 380/400/415V |
| Rated Frequency | 50Hz |
| Power Factor | 0.8 |
| Rated Power | 344kW / 430kVA |
| Insulation Class | H |
| Temperature Rise Class | H |
| Protection Class | IP23 |
| Ambient Temperature | 40 deg C |
| Altitude | <= 1000 m |
| Phases | 3 |
| Winding Pitch | 2/3 |
| Excitation System | Self-excitation |
| Number of Bearings | 1 |
| Connection Type | Star |
| Poles | 4 |
| Waveform Distortion (THD) | < 5% |
| Telephone Interference Factor (THF) | < 2% |
Control System
The standard SWT control system is designed for single-unit generator operation. It supports local and remote start, engine and alternator parameter detection, control and protection functions, event logs and multiple communication interfaces.
- LCD screen with key operation
- Multilingual display
- Engine and alternator parameter detection
- Local and remote start functions
- Control and protection functions
- Event logs with real-time clock
- Multiple communication interfaces available
- IP65 overall protection available according to configuration
ATS Optional
An ATS panel can be supplied for automatic transfer between mains power and generator power. The ATS controller combines measurement, display and control functions for mains-to-mains or mains-to-generator applications.
- Microcomputer control and all-digital technology
- LCD display for ATS status and operation mode
- Voltage and frequency measurement through LCD display
- Fast on-load switching of two power sources, with switching time <= 80 ms
- Electrical and mechanical double interlock design to prevent short circuit between power sources
- Communication function available with optional communication module
SWT Paralleling System Optional
For projects requiring multiple generator sets, the SWT paralleling system supports genset-to-genset and genset-to-grid applications. The system can synchronize up to 32 units automatically and can select the appropriate number of running units according to load demand.
- Automatic start and automatic synchronizing operation
- Supports genset-to-genset, genset-to-grid and paralleling with ATS
- Can automatically add or remove units according to load demand
- PLC system and touch screen available upon request
- Built-in fault detection and Chinese/English operation interface
- Convenient capacity expansion for future projects
Applications
The SWT 360kW / 450kVA Cummins diesel generator set is suitable for a wide range of industrial, commercial and standby power applications. Typical applications include:
- Industrial plants and manufacturing facilities
- Commercial buildings and office complexes
- Construction sites and temporary power projects
- Mining sites and remote operation areas
- Oilfield and energy projects
- Hospitals and public facilities
- Telecom stations and infrastructure projects
- Data centers and critical backup power systems
- Emergency standby power supply
Why Choose SWT 360kW / 450kVA Diesel Generator Set?
- Reliable Cummins engine: equipped with a Cummins KTA19-G3 engine for stable power output and dependable operation.
- Flexible configuration: open type, silent type and super silent type are available for different installation environments.
- Factory-tested before delivery: each generator set passes load tests and inspection of protection devices and control systems before shipment.
- Project adaptation: voltage, enclosure, fuel system, control system, ATS and paralleling system can be customized according to project needs.
- Easy operation and monitoring: LCD control system, event logs and multiple communication interfaces support easier operation and maintenance.
- Suitable for single-unit or multi-unit systems: SWT paralleling system can support larger power projects and future expansion.
Standard Accessories
- Engine, alternator, chassis and control box
- Controller for single unit
- Circuit breaker up to 1200kW
- Industrial muffler, muffler flange and bellow joint
- Shock absorber
- Test report, certificate of quality and schematic diagram
- Installation manual and operation manual
Optional Accessories
- Daily fuel tank or bulk fuel tank
- Residential silencer
- Power cable
- Anti-condensation heater for alternator
- Battery charger, water jacket heater and oil heater
- Fuel level sensor, auto oil make-up device and auto fuel filling device
- Soundproof enclosure, containerized enclosure and trailer
- Exhaust pipe and hot air discharge duct
- RS485 extension module, Ethernet communication and cloud monitor
- ATS panel, motorized circuit breaker and synchronizing system
- Deepsea, ComAp and SmartGen controller options
- Spare parts
FAQ
Q: What is the prime power of this generator set?
A: The prime power is 360kW / 450kVA. It is suitable for continuous operation under variable load conditions.
Q: What is the standby power of this generator set?
A: The standby power is 400kW / 500kVA. Standby power is intended for emergency use, with no overload allowed.
Q: What engine does this generator set use?
A: This generator set is powered by a Cummins KTA19-G3 diesel engine.
Q: What voltage and frequency are available?
A: The standard frequency is 50Hz, and the rated voltage can be 380V, 400V or 415V. Other voltage requirements can be customized according to project needs.
Q: Is a silent type available?
A: Yes. Open type, silent type and super silent configurations are available.
Q: Can this generator set work with an ATS panel?
A: Yes. An ATS panel is available as an optional accessory for automatic transfer between mains power and generator power.
Q: Can multiple units operate in parallel?
A: Yes. SWT can provide a paralleling system for genset-to-genset or genset-to-grid applications, supporting up to 32 units for automatic synchronization.
Q: What tests are carried out before delivery?
A: Each generator set passes load tests at 0%, 25%, 50%, 75%, 100% and 110%, as well as inspection of protection devices and control systems before delivery.
Q: What applications is this generator suitable for?
A: It is suitable for industrial plants, construction sites, mining projects, oilfield projects, commercial buildings, telecom stations, data centers and emergency backup power applications.